Electrical Panel Infrared Thermography Inspection Checklist
This standard operating procedure details the process for conducting infrared thermography inspections on low- and medium-voltage electrical panels. It covers pre-inspection safety, camera setup, thermal scanning techniques, and documentation requirements to identify loose connections, overloaded circuits, and failing components.
The purpose of this SOP is to establish a consistent and safe method for using infrared thermography to detect abnormal temperature patterns in electrical equipment. Proactive identification of hotspots prevents arc flash incidents, unplanned downtime, and equipment damage. This checklist ensures that every inspection follows the same critical steps, from hazard assessment to final reporting.
This procedure applies to all energized electrical panels rated up to 600 VAC in industrial, commercial, and institutional facilities. It covers both enclosed (cover-on) scanning and open-panel scanning after lockout/tagout. This SOP is intended for qualified electrical workers who have completed thermal imaging training and are familiar with CSA Z462 arc flash safety requirements. It does not apply to high-voltage switchgear (>600 V) without additional approvals.
- Lockout/Tagout must be applied before opening any panel cover that exposes energized parts. Verify absence of voltage with a rated proximity tester after LOTO.
- Wear arc‑rated PPE (face shield, balaclava, switching jacket, gloves) in accordance with the incident energy analysis. Minimum category 2 for most 480 V panels. Remove metallic jewelry.
- After scanning, allow 5 minutes for components to cool before touching. Hot surfaces may cause burns even at moderate temperature differentials.
- Thermal imaging camera (minimum 160×120 resolution, with emissivity and reflected temperature compensation)
- Arc flash rated PPE (face shield, gloves, jacket, balaclava, voltage-rated leather or rubber gloves)
- Lockout/tagout kit (padlocks, hasps, danger tags, LOTO checklist)
- Insulated hand tools (screwdrivers, nut drivers) rated for the panel voltage
- Non‑contact voltage tester (CAT IV rated)
- Inspection form / digital checklist (paper or app)