Exit Sign And Emergency Lighting Monthly Test
Comprehensive procedure for verifying the operation of exit signs and emergency lighting units under NFPA 101 / Life Safety Code. Includes visual inspection, battery endurance test, and documentation requirements for industrial facilities.
To ensure all exit signs and emergency lighting units in the facility are functional, adequately illuminated, and compliant with NFPA 101 and local fire codes. Monthly testing identifies battery degradation, lamp failures, and physical damage before an actual emergency occurs.
This procedure applies to all permanently installed exit signs (self-luminous and electric) and emergency lighting units (including remote heads and central battery systems) within the main production building, warehouse, office areas, and exterior egress paths. It covers the monthly 30‑second functional test and the required visual inspection. Annual 90‑minute full discharge tests are covered under a separate SOP. This procedure is for use by maintenance technicians, safety coordinators, and designated floor personnel.
- Before disconnecting power to emergency circuits, verify that normal lighting is present in the area. If testing a single circuit, ensure other emergency units in the zone remain active per code.
- Use an approved step ladder or ladder lift to reach ceiling-mounted units. Never stand on a forklift or makeshift platform.
- Wear safety glasses when handling lamps or batteries. Gloves required if replacing glass tubular lamps or sealed batteries.
- Do not touch exposed terminals on battery connections. Short‑circuit current can cause arc flash. Wear rubber gloves rated for DC voltage if handling connections.
- Step ladder (as required for unit height)
- Flashlight (for visual inspection)
- Digital timer or stopwatch
- Facility map with all exit signs and emergency lights plotted
- Log sheet (paper or digital) – with columns for date, time, unit ID, visual check pass/fail, 30‑sec test pass/fail, remarks
- Replacement lamps (LED or incandescent as per unit spec)
- Replacement batteries (sealed lead‑acid or Ni‑Cd as per unit spec)
- Insulated screwdrivers, small insulated pliers
- Anti‑static wrist strap (if handling circuit boards)