Warehouse Eyewash Station Monthly Activation Check
Mandatory monthly activation test procedure for all plumbed and self-contained eyewash stations in warehouse and industrial environments. Ensures compliance with ANSI Z358.1, WorkSafeBC OHS Regulation Part 7, and CSA Z432 standards for emergency eyewash equipment.
To verify that every eyewash station in the facility delivers a sufficient, tepid, and unobstructed flow of flushing fluid within one second of activation. Monthly activation testing prevents nozzle corrosion, sediment buildup, and bacterial growth from rendering the station inoperable during a chemical exposure emergency. This procedure also confirms that flow rate, stream pattern, and water temperature meet the minimum requirements of ANSI Z358.1-2014 and WorkSafeBC OHS Regulation Part 7, Section 7.2.
This SOP applies to all fixed and portable eyewash stations located within the warehouse, shipping/receiving docks, battery charging areas, chemical storage rooms, and any other zone where corrosive or irritating substances are handled. Both plumbed (piped water supply) and self-contained (gravity-feed or pressurized fluid cartridge) units are covered. Excluded: Drench showers, combination units (eyewash + shower), and vehicle-mounted portable stations — each has its own dedicated SOP.
- Lockout/Tagout any powered eyewash station (heated, alarmed, or self-contained with electric pump) at the breaker panel before opening access panels. Verify zero energy state with a contactless voltage tester.
- If the eyewash station is located in a chemical storage area, verify that the area is free of active spills and that the ventilation system is operating before beginning the test. Wear chemical-resistant gloves and safety glasses when handling any flushing fluid that may be contaminated.
- Contain all discharged water with a catch basin or bucket. The floor surface near the eyewash station may become slippery — deploy absorbent mats or caution signage in high-traffic zones.
- Verify that flushing fluid temperature falls between 15°C and 37°C. Water above 38°C can cause chemical absorption and tissue damage. If the water is scalding hot, tag the unit out of service immediately and contact maintenance.
- Eyewash station activation test tag or log card (paper or digital)
- Stopwatch or timer (smartphone timer acceptable)
- Clean bucket or catch basin (minimum 5 L capacity)
- Disposable absorbent towels or shop rags
- Pen or permanent marker
- Distilled water (for refill of self-contained units only, if required)
- Safety glasses and nitrile gloves
- Multi-tool or adjustable wrench (for opening sealed cartridge compartments)
- Thermometer (infrared or immersion, optional but recommended)