Maintenance & Reliability · Log Form

Chiller Preventive Maintenance Daily / Weekly / Monthly Log Sheet

Standardised log for recording daily, weekly, and monthly preventive maintenance checks on industrial chillers. Covers refrigerant pressures, condenser coil condition, water treatment parameters, electrical integrity, safety cutouts, and corrective actions — all in one auditable form.

Frequency
Daily / Weekly / Monthly
Department
Maintenance
Asset Type
Centrifugal / Screw / Scroll Chiller
Version
2.1
Free download — no sign‑up, no email.Take this log to your shop floor and mount it on a clipboard.
Overview & Purpose

This log sheet provides a structured daily, weekly, and monthly inspection regime for industrial chillers. It captures critical operating parameters — suction/discharge pressures, condenser approach temperature, oil level, refrigerant charge, water treatment chemistry, electrical insulation values, and safety cutout functionality — ensuring proactive detection of degradation before unplanned downtime. Compliance with ASHRAE 15, CSA B52, and manufacturer warranty requirements is supported through consistent documentation.

Equipment & Safety Prerequisites
  • LOTOLockout/Tagout — isolate chiller electrical disconnect and verify zero energy before opening panels or accessing refrigerant circuits. Use group LOTO if multiple technicians are involved.
  • PPERequired PPE: safety glasses, cut-resistant gloves, dielectric boots, hearing protection (if compressor enclosure is opened). Carry refrigerant-grade gloves and face shield when handling refrigerant.
  • TOOLRequired tools: manifold gauge set, thermometer/pyrometer, refrigerant leak detector (electronic or UV), megger (500 V), water test kit (pH, conductivity, inhibitor level), and manufacturer O&M manual.
  • ENVEnvironmental conditions: chiller room must be well-ventilated. If refrigerant leak is suspected, use continuous monitoring and evacuate if concentration exceeds 1,000 ppm.

Inspection / Log Matrix

Status (P/F) Inspection Item / Task Tolerance / Threshold Actual Reading
[ ] Pass [ ] Fail Suction pressure (low side) — each circuit Per OEM spec ± 5 % ______ psig
[ ] Pass [ ] Fail Discharge pressure (high side) — each circuit Per OEM spec ± 5 % ______ psig
[ ] Pass [ ] Fail Oil level in sight glass — each compressor Between ¼ and ¾ sight glass ______ / ¾
[ ] Pass [ ] Fail Condenser approach temperature ≤ 10 °F (5.5 °C) above ambient ______ °F / °C
[ ] Pass [ ] Fail Evaporator approach temperature ≤ 6 °F (3.3 °C) above setpoint ______ °F / °C
[ ] Pass [ ] Fail Refrigerant sight glass — moisture indicator Green (dry) / yellow (wet) — must be dry _____ / dry
[ ] Pass [ ] Fail Condenser coil cleanliness — visual & pressure drop No visible debris; ΔP ≤ 1.5 × clean baseline ______ inH₂O
[ ] Pass [ ] Fail Water treatment — pH, conductivity, inhibitor residual pH 7.0–8.5; cond. < 600 µS/cm; inhibitor > 80 % pH ___ / ___ µS
[ ] Pass [ ] Fail Flow switch operation — evaporator & condenser Closes within 5 s of flow established ______ s
[ ] Pass [ ] Fail Vibration — compressor bearing housing (velocity) ≤ 0.25 in/s (6.4 mm/s) peak ______ in/s
[ ] Pass [ ] Fail Electrical — megger test (motor windings to ground) ≥ 1 MΩ at 500 V; trending no drop > 25 % ______ MΩ
[ ] Pass [ ] Fail Safety cutouts — high-pressure, low-pressure, freeze-stat Each trips within spec; reset manually verified ______ / ______ / ______

Stop Chasing Maintenance Blindly

Track every calibration, pressure drop reading, and machine performance trend in one place. ServiceGrid logs your tasks automatically and alerts you before failure.

Try ServiceGrid →

Defect / Corrective Action Log

Date / Time Item # Issue Identified Corrective Action Taken WO #
___/___/_____ _______ _______________________________ _______________________________ _______
___/___/_____ _______ _______________________________ _______________________________ _______
___/___/_____ _______ _______________________________ _______________________________ _______
___/___/_____ _______ _______________________________ _______________________________ _______
___/___/_____ _______ _______________________________ _______________________________ _______
Sign-Off & Verification

By signing below, the inspector verifies that all items have been checked according to the manufacturer's specifications and facility safety standards. Any out-of-tolerance condition has been recorded in the Defect / Corrective Action Log.

Inspector Name / Signature
Date & Time
Supervisor Review / Sign-Off
Date