Maintenance & Reliability · Log Form

Spray Booth Airflow And Filter Maintenance Log

Daily / shift-level record of spray booth airflow velocity, differential pressure across filters, and visual inspections. Ensures compliance with NFPA 33, OSHA 1910.107, and local fire codes. Use this log to document pass/fail status and trigger corrective actions before coating defects or safety incidents occur.

Frequency
Daily / Shift
Department
Maintenance
Asset Type
Spray Booth
Version
1.0
Free download — no sign‑up, no email.Take this log to your spray booth and mount it on a clipboard.
Overview & Purpose

This log captures critical airflow and filter integrity data for spray booths used in painting, coating, and finishing operations. Each row in the inspection matrix must be completed at the start of every shift or following booth idle periods exceeding 4 hours. Air velocity at the booth face shall be maintained at 100 ± 10 ft/min (0.51 ± 0.05 m/s) for crossdraft booths and 60–100 ft/min for downdraft designs. Filter differential pressure must not exceed the manufacturer’s recommended maximum (typically 2.0 in. w.g. for pre-filters and 1.5 in. w.g. for final HEPA filters). Exceedances trigger an immediate corrective action.

Equipment & Safety Prerequisites
  • LOTOLockout/tagout of spray booth exhaust fan before any filter change or cleaning operation. Verify zero energy state.
  • PPEWear appropriate PPE: safety glasses, nitrile gloves, and respirator if handling used filters. No open flames or spark-producing tools within 20 ft.
  • INSTRequired instruments: calibrated hot-wire anemometer (±3% accuracy), Magnehelic or digital manometer (range 0–5 in. w.g.), LED flashlight, and booth manufacturer’s manual.

Inspection / Log Matrix

Status (P/F) Inspection Item / Task Tolerance / Threshold Actual Reading
[ ] Pass [ ] Fail Exhaust fan operational and guard in place Fan runs, no abnormal noise, interlock works _________________
[ ] Pass [ ] Fail Booth face airflow velocity (crossdraft) 100 ± 10 ft/min ________ ft/min
[ ] Pass [ ] Fail Downdraft booth airflow (if applicable) 60–100 ft/min at floor ________ ft/min
[ ] Pass [ ] Fail Pre-filter differential pressure (first stage) ≤ 2.0 in. w.g. (replace at 1.8) ________ in. w.g.
[ ] Pass [ ] Fail HEPA final filter differential pressure ≤ 1.5 in. w.g. ________ in. w.g.
[ ] Pass [ ] Fail Booth walls, floor, and ceiling integrity No holes, tears, or gaps > 1/8 in. Comments: __________
[ ] Pass [ ] Fail Lighting fixtures functional and sealed All lamps illuminate, no cracked lenses _________________
[ ] Pass [ ] Fail Fire suppression system pressure gauge Needle within green zone (125–175 psi) ________ psi
[ ] Pass [ ] Fail Explosion-proof electrical and bonding All covers tight, ground strap intact _________________

Stop Chasing Maintenance Blindly

Track every calibration, pressure drop reading, and machine performance trend in one place. ServiceGrid logs your tasks automatically and alerts you before failure.

Try ServiceGrid →

Defect / Corrective Action Log

Date / Time Item # Issue Identified Corrective Action Taken WO #
___/___/_____ _______ _______________________________ _______________________________ _______
___/___/_____ _______ _______________________________ _______________________________ _______
___/___/_____ _______ _______________________________ _______________________________ _______
Sign-Off & Verification

By signing below, the inspector verifies that all items have been checked according to the manufacturer's specifications and facility safety standards. Any failures recorded in the Inspection Matrix have been transferred to the Corrective Action Log.

Inspector Name / Signature
Date & Time
Supervisor Review (if applicable)
Date