Building Fire Alarm Control Panel Monthly Walk Test
This procedure ensures the reliability of the building fire alarm system through a systematic monthly inspection and functional test of the Fire Alarm Control Panel (FACP) and all connected initiating and notification devices.
To verify that the Fire Alarm Control Panel (FACP) and all connected initiating devices (smoke detectors, heat detectors, manual pull stations) and notification appliances (strobes, horns) are functioning correctly. This monthly walk test ensures early detection of faults, compliance with code requirements, and reliability of the fire alarm system in an industrial setting.
This procedure applies to all Fire Alarm Control Panels installed in industrial facilities within the scope of the facility's fire safety plan. It covers visual inspection, battery load testing, alarm activation and reset, and communication verification to the monitoring station. Excludes annual full‑function testing as required by NFPA 72, which must be performed by a certified fire protection contractor.
- Always notify the monitoring station and facility personnel before starting the test to prevent false dispatches. Obtain verbal confirmation from the monitoring station that the system is in test mode.
- For any work requiring contact with wiring or terminals inside the FACP cabinet, perform lockout/tagout on the building's fire alarm branch circuit. Only qualified electricians may open the panel.
- Wear safety glasses and hearing protection when testing audible notification appliances. Use a ladder rated for your weight when reaching ceiling‑mounted detectors.
- Keep a minimum 10‑lb ABC fire extinguisher in the immediate area during testing. If an actual fire alarm occurs during the test, follow emergency response procedures immediately.
- Do not bypass any safety interlocks or disable the system for longer than necessary. After testing, ensure the system is fully restored to normal operation.
- FACP keys (panel cabinet key, battery compartment key)
- Digital multimeter (rated for battery voltage testing)
- Two‑way radios or dedicated communication line with monitoring station
- Safe ladder (Class I or II) for accessing ceiling‑mounted detectors
- Spare backup batteries (lead‑acid or NiCd as per manufacturer spec)
- Clean, lint‑free cloth and electronic contact cleaner
- Facility logbook or digital device with SafeDesk app for recording
- Personal protective equipment (safety glasses, hearing protection)
- ABC fire extinguisher (minimum 10 lb)