Safety & Compliance · Form & Log

Hot Work Fire Watch Log

Mandatory fire watch documentation for welding, cutting, grinding, brazing, and any operation producing open sparks or open flames. This log satisfies WorkSafeBC OHS Regulation Part 12 (Fire Prevention) and NFPA 51B requirements for continuous and post-work fire monitoring.

Frequency
Per Hot Work Event
Department
Health & Safety
Regulation
NFPA 51B · WorkSafeBC 12
Version
1.0
Free download — no sign‑up, no email.Take this permit or log to your shop floor and mount it on a clipboard.
Overview & Purpose

This fire watch log documents every hot work event from ignition to final clearance. It enforces the mandatory fire watch procedures required by NFPA 51B and WorkSafeBC OHS Regulation Part 12. The log captures pre-work hazard assessment, hourly monitoring checks, post-work fire watch (minimum 30 minutes), and supervisor sign-off. Using this log ensures audits are demonstrable and that spark-producing operations never run without a trained fire watcher stationed with appropriate extinguishing equipment.

Hazard Assessment Prerequisites
  • HAZARDCombustible materials within 11 m (36 ft) of hot work area have been removed or covered with fire‑resistant blankets.
  • PPEFire watcher is equipped with fire‑resistant clothing, eye protection, and a charged extinguisher (minimum 4‑A:40‑B:C rated) readily accessible.
  • CHECKHot work equipment (torch, regulator, hoses) inspected for leaks and damage; flashback arrestors installed.
  • CHECKAll nearby personnel have been notified; warning signs and barriers posted.
  • ATMOSIf hot work is near combustible gas or vapour sources, an atmospheric test for LEL (< 10% LEL) has been performed and documented.

Audit / Inspection Matrix

Status (P/F) Checklist Item / Hazard Compliance Standard Action Required / Notes
[ ] Pass [ ] Fail Fire extinguisher fully charged, inspected within last 12 months, and located within 15 seconds of the hot work zone. NFPA 10, WorkSafeBC 12.10 _________________
[ ] Pass [ ] Fail Designated fire watcher is present, competent, and not performing any other task during the hot work. NFPA 51B (7.2.2) _________________
[ ] Pass [ ] Fail Combustible flooring (wood, rubber) within 11 m is covered with wet down, sand, or fire‑resistant blankets. NFPA 51B (6.3) _________________
[ ] Pass [ ] Fail All walls, ceilings, and openings that could allow sparks to travel to adjacent spaces are sealed or monitored. NFPA 51B (6.5) _________________
[ ] Pass [ ] Fail Post‑work fire watch: continuous monitoring of hot work area and adjacent zones for at least 30 minutes after work stops. NFPA 51B (5.4.8) _________________

Digitize Your Safety & Compliance

Throw away the paper checklists. Have your operators complete safety audits, crash reports, and daily inspections directly on their phones using SafeDesk. Stay compliant with WorkSafeBC without the administrative bloat.

Try SafeDesk →

Incident / Corrective Action Log

Date / Time Item # Safety Issue Identified Corrective Action Taken Assigned To
___/___/_____ 1 _______________________________ _______________________________ _______
___/___/_____ 2 _______________________________ _______________________________ _______
___/___/_____ 3 _______________________________ _______________________________ _______
Supervisor Sign-Off & Verification

By signing below, the supervisor or designated competent person verifies that all fire watch checks, atmospheric tests, and post‑work monitoring have been completed according to NFPA 51B and company policy. The hot work area has been left in a safe condition.

Supervisor Name / Signature
Date & Time