Spill Prevention Control And Countermeasure SPCC Monthly Audit
This procedure covers the required monthly inspection of aboveground storage tanks, secondary containment, piping, and spill response equipment to maintain compliance with EPA 40 CFR Part 112 (SPCC).
The purpose of the SPCC Monthly Audit is to verify that all oil storage containers, secondary containment structures, and spill control equipment are in good working order and free from leaks or damage. This inspection ensures compliance with the facility's SPCC Plan and reduces the risk of a discharge to navigable waters or adjoining shorelines.
This SOP applies to all facilities subject to EPA SPCC regulations that store oil in aboveground storage tanks (ASTs) with a total capacity greater than 1,320 gallons (or 660 gallons in a single container). The monthly inspection covers the tank exterior, foundation, secondary containment, piping, valves, and spill response readiness. It does not replace the mandatory annual SPCC inspection or periodic integrity testing.
- Lockout/tagout any tank valves, pumps, or equipment before performing close visual or touch inspections. Ensure energy sources are isolated.
- Wear safety glasses, chemical-resistant gloves, steel-toed boots, and a hard hat when entering containment areas. Use a NIOSH-approved respirator if vapours are suspected.
- Beware of slip, trip, and fall hazards in containment dikes—standing water, ice, or oil residue can make surfaces treacherous. Use caution when walking on tank top platforms.
- Have an emergency spill kit immediately accessible before beginning the inspection. Know the location of the nearest eyewash station and safety shower.
- SPCC inspection checklist (digital or printed copy of the facility's checklist form)
- Flashlight (high-lumen, intrinsically safe for classified areas if required)
- Spill kit contents list and verification sheet
- Camera or smartphone with camera for photographic documentation
- PPE as listed in safety precautions above
- Measuring tape (e.g., 25 ft) or calibrated dipstick for verifying tank levels
- Logbook, tablet, or clipboard with waterproof paper
- Lockout/tagout kit (if isolating any equipment during inspection)