Building Automation System BAS Sensor Calibration Verification
This procedure outlines the steps to verify the calibration accuracy of field-mounted BAS sensors (temperature, humidity, differential pressure, CO2) against a NIST-traceable reference. Regular verification ensures energy efficiency, occupant comfort, and reliable equipment control.
To ensure all Building Automation System (BAS) sensors (temperature, humidity, differential pressure, CO₂) provide readings within manufacturer tolerance. Incorrect sensor data leads to energy waste, system short-cycling, and comfort complaints. Regular verification — at intervals specified by the plant reliability program — catches drift before it affects control logic.
This SOP applies to all field-mounted sensors wired to any BAS controller (Niagara, Distech, Siemens, Johnson Controls, etc.). Verification is performed using NIST-traceable handheld instruments. Results are recorded in the CMMS and a physical calibration tag is affixed.
This procedure covers:
- All hard-wired and wireless room sensors, duct sensors, outside air sensors, and immersion sensors.
- Typical sensor types: 10K/20K NTC thermistors, 4–20 mA transmitters, 0–10 VDC sensors, and resistive RH elements.
- Verification does not include destructive testing, sensor removal for bench calibration, or repair — those are covered under separate recalibration PMs.
- Performed quarterly on a rotating basis or when a point is flagged by the BAS analytics engine.
- If the sensor location requires opening a controller panel or working near live 24 VAC/VDC terminals, complete lockout/tagout per site LOTO procedure. Do not bypass safety interlocks.
- When accessing sensors mounted 2 m or higher, use an approved ladder or lift. Maintain 3-point contact. Do not overreach — move the ladder instead.
- Wear safety glasses and nitrile gloves when handling reference instruments near ductwork or mechanical rooms. If working in an area with moving equipment, also wear high-visibility vest.
- When using CO₂ calibration gas (e.g., 1000 ppm cylinder), secure the bottle to prevent tip‑over. Ventilate the area after calibration. Do not inhale directly.
- Handheld temperature/humidity reference (e.g., Fluke 971, Testo 605i, or Rotronic HC2A-S). Must have current calibration certificate.
- Differential pressure manometer (e.g., Dwyer 475-1 Mark III) with silicone tubing.
- CO₂ calibration gas kit: certified cylinder at 400 ppm or 1000 ppm with regulator and regulator-to-sensor adapter.
- Laptop or tablet with BAS front‑end software (Niagara Workbench, Distech EC‑gfx, or manufacturer tool).
- Small flat‑head screwdriver (for terminal blocks if sensor needs removal for bench check).
- Calibration tags (non‑metallic, zip‑tie style) and permanent marker.
- ServiceGrid (or other CMMS) for digital logging. (See inline ad below.)