Maintenance & Reliability · Log Form

Emergency Standby Diesel Generator Monthly Load Bank Testing

This log form documents the monthly load bank test procedure for emergency standby diesel generators in critical power applications. It captures pre-test conditions, step-load data, fluid thresholds, and any corrective actions required to maintain NFPA 110 compliance and manufacturer warranty requirements.

Frequency
Monthly
per NFPA 110
Department
Maintenance
Electrical / Mechanical
Asset Type
Diesel Generator
150 kW – 2.5 MW
Version
2.1
Rev. Feb 2026
Free download — no sign‑up, no email.Take this log to your shop floor and mount it on a clipboard.
Overview & Purpose

Monthly load bank testing is required to prevent wet stacking — a condition where unburned fuel and carbon accumulate in the exhaust system during prolonged low-load or no-load operation. This test applies a resistive load at 25%, 50%, 75%, and 100% of nameplate kW rating while logging voltage, frequency, oil pressure, coolant temperature, and exhaust temperature at each step. Any parameter exceeding the tolerances listed in the matrix below triggers a corrective action entry. This log serves as the auditable record for NFPA 110 Level 1 compliance, insurance inspections, and the generator manufacturer's warranty terms.

Equipment & Safety Prerequisites
  • LOTOVerify automatic transfer switch (ATS) is in 'test' position and generator breaker is closed. Apply lockout/tagout on any remote start signals from the building management system. Confirm load bank ground bond is intact and rated for full test current.
  • ARCPersonal Protective Equipment: arc-rated coverall (minimum 8 cal/cm²), voltage-rated gloves (Class 0), safety glasses, hearing protection, and steel-toed boots. No loose clothing near the radiator fan or belt drive.
  • FUELFuel supply must be at least 75% full before starting the test. Confirm day tank level, return line integrity, and that the fuel supply pump is in 'auto'. Have a Class B fire extinguisher (minimum 20 lb) within 10 metres of the generator set.
  • COOLCoolant system must be pressurized and at operating temperature (minimum 30°C) before applying load. Confirm block heater is functioning and that the radiator shutters or fan clutch cycles freely. Top off coolant if necessary — do not open pressurized cap above 50°C.

Inspection / Load Bank Test Matrix

Status (P/F) Inspection Item / Task Tolerance / Threshold Actual Reading
[ ] Pass [ ] Fail Coolant level & freeze protection Level within 2.5 cm of filler neck; specific gravity ≤ –35°C _________________
[ ] Pass [ ] Fail Engine oil level & pressure (at idle, hot) Oil at full mark on dipstick; pressure 40–55 psi @ 1800 rpm _________________
[ ] Pass [ ] Fail Battery voltage (rest / under crank) ≥ 12.4 V rest (12 V system); ≥ 9.6 V during cranking _________________
[ ] Pass [ ] Fail Block heater temperature (coolant jacket) ≥ 30°C measured at thermostat housing _________________
[ ] Pass [ ] Fail Voltage at 25% load (L–L average) 208/480 V ± 2% (203–212 V / 470–490 V) _________________
[ ] Pass [ ] Fail Voltage at 50% load (L–L average) 208/480 V ± 3% (202–214 V / 466–494 V) _________________
[ ] Pass [ ] Fail Voltage at 75% load (L–L average) 208/480 V ± 4% (200–216 V / 461–499 V) _________________
[ ] Pass [ ] Fail Voltage at 100% load (L–L average) 208/480 V ± 5% (198–218 V / 456–504 V) _________________
[ ] Pass [ ] Fail Frequency at all load steps 60 Hz ± 0.5 Hz (59.5–60.5 Hz) _________________
[ ] Pass [ ] Fail Exhaust temperature (each bank, at 100% load) 350–550°C (individual cylinder within 50°C of average) _________________
[ ] Pass [ ] Fail Coolant temperature (at 100% load, steady-state) 82–96°C (thermostat rated temp ± 5°C) _________________
[ ] Pass [ ] Fail Oil temperature (at 100% load) ≤ 120°C measured at pan drain plug _________________
[ ] Pass [ ] Fail Cool-down period after 100% load removal Minimum 5 minutes unloaded before shutdown ____ min
[ ] Pass [ ] Fail Post-test visual inspection (leaks, vibration, noise) No fluid leaks, no abnormal vibration or knocking _________________

Stop Chasing Maintenance Blindly

Track every calibration, pressure drop reading, and machine performance trend in one place. ServiceGrid logs your tasks automatically and alerts you before failure.

Try ServiceGrid →

Defect / Corrective Action Log

Date / Time Item # Issue Identified Corrective Action Taken WO #
___/___/_____ ___:___ _______ _______________________________ _______________________________ _______
___/___/_____ ___:___ _______ _______________________________ _______________________________ _______
___/___/_____ ___:___ _______ _______________________________ _______________________________ _______
___/___/_____ ___:___ _______ _______________________________ _______________________________ _______
___/___/_____ ___:___ _______ _______________________________ _______________________________ _______
Sign-Off & Verification

By signing below, the inspector verifies that all load bank test steps have been executed in accordance with NFPA 110 Section 8.4.1 and the generator manufacturer's published service intervals. All out-of-tolerance readings have been recorded in the Corrective Action Log.

Inspector Name / Signature
Date & Time
Reviewing Supervisor / Signature
Date & Time