Industrial HVAC Roof Top Unit (RTU) Filter Replacement
Standard procedure for replacing 2-inch pleated MERV-8 filters on packaged roof top units to maintain indoor air quality, equipment efficiency, and prevent excessive static pressure.
This procedure defines the approved method for replacing 2-inch pleated MERV-8 air filters in packaged roof top units (RTUs) at industrial facilities. Correct filter replacement maintains indoor air quality within regulatory limits, prevents fan motor overload due to excessive static pressure, and extends the service life of the heating/cooling coils. Compliance with this SOP ensures consistent airflow and energy-efficient operation of the HVAC system.
This SOP applies to all single-zone and multi-zone packaged RTUs rated between 5–50 tons installed in industrial buildings, warehouses, and workshops. It covers filter access, inspection, removal, disposal, and installation of new filters. It does not cover economizer damper adjustment, fan belt replacement, or coil cleaning operations. Tasks beyond filter replacement require a separate work permit and qualified HVAC technician.
- Lock out the RTU disconnect switch at the unit. Verify zero energy by attempting a start command from the thermostat or BMS override. Do not rely on remote shutdown alone.
- Wear cut-resistant gloves (ANSI A4 minimum), safety glasses with side shields, and a NIOSH-approved N95 respirator when handling soiled filters. Replace respirator if moisture or damage occurs.
- If the RTU is installed at a height ≥ 6 ft above grade, use a properly anchored safety harness and lanyard (CSA Z259.10). Ensure access platform or ladder is rated for industrial use.
- Used filters may contain mould, bacteria, and respirable dust. Do not blow dust off filters. Seal immediately in a heavy-duty garbage bag. Dispose as per local environmental regulations.
- Replacement filters (nominal 2" × 24" × 24", MERV-8 or equivalent — verify dimensions on existing filter label)
- Flashlight (headlamp recommended)
- Cut-resistant gloves (ANSI A4 minimum)
- Heavy-duty garbage bags
- Strap wrench (if filter retaining clips are seized)
- Marker or label to record filter size and direction of airflow
- HEPA vacuum cleaner with crevice tool (for debris removal in the filter rack)
- Lockout/tagout kit (padlock, hasp, danger tag)
- Safety harness and lanyard (if fall hazard exists)